Voltage: 230 VAC 50/60 Hz
Power consumption: 10-75 W depending on pump speed
Working temperature: Min. +5°C/Max. +100°C
Ambient temperature: Min. +5°C/Max. +58°C
Max. working pressure: 1.0 MPa (10 bar)
Leakage: < 0,2% of Kvs at 100 kPa
Media 1: Water - Ethylene glycol mixture max. 50%
Thread standard: G - male thread, R - female thread
Circulating pumps: Wilo PARA 25-180/8-75/SC-12
Material, valve body: Brass EN 12165 CW617N
Material, insulation: Expanded Polypropylene EPP
Dimensions: 248 x 463 x 165 mm
Weight: 6,2 kg
Manufacturer: LK Armatur AB
DATASHEET LK HydronicGroup 125
INSTRUCTION MANUAL LK 860, 861, 862 HydronicGroup
Pump group LK 862 HydronicGroup 125 R. Complete pump group that is suitable for heating systems where direct supply or mixed supply is desirable. Pump group LK 862 comprises a highly efficient circulation pump, insulation, wall mounting bracket and two ball valves with thermometer, of which the ball valve on the return side has an integrated check valve, three-way mixing valve Kvs 10 m3/h